Mersen AMP-TRAP 2000 SmartSpot ATDR15 Current Limiting North American Time Delay Power Fuse, 15 A, 600 V AC, 200 kA Interrupt, CC Class, Cylindrical Body
Ferraz Shawmut ATDR15
Mersen AMP-TRAP 2000 SmartSpot ATDR15 Current Limiting North American Time Delay Power Fuse, 15 A, 600 V AC, 200 kA Interrupt, CC Class, Cylindrical Body
In Stock: 783more info
|
BrandFerraz Shawmut
MFG #ATDR15
Werner Part #32718
UPC782001901103
In Stock: 783more info
|
BrandFerraz Shawmut
MFG #ATDR15
Werner Part #32718
UPC782001901103
Product Description
Mersen AMP-TRAP 2000 SmartSpot Power Fuse, Current Limiting North American Time Delay, Series: ATDR, Non-Indicating, Rejection, 15 A, 600 V AC, 200 kA Interrupt, Class: CC, Ferrule Terminal, Clip Mounting, Cylindrical Body, Dual Element, Fiberglass, 13/32 in Dia x 1-1/2 in L Body
Attributes
Documents
Applications
Features
Attributes
Body Size13/32 in Dia x 1-1/2 in L
Body TypeCylindrical
ClassCC
Country of OriginMX
ElementDual
Indicating/Non-IndicatingNon-Indicating
Interrupt Rating200 kA
ManufacturerMERSEN
MaterialFiberglass
Mounting TypeClip
Package TypeEACH
Rejection/Non-RejectionRejection
SeriesATDR
Terminal TypeFerrule
Type / StyleCurrent Limiting North American Time Delay
Small Motor, Contactor, Branch Circuit Protection, Lighting, Heater, General Loads, Conventional Energy, Renewable Energy and Alternative Energy Generation, Datacenters, IT Space - CI, Hyper Converged, Marine Vessels and Equipment Applications
Features
Time delay for motor starting inrush currents without nuisance opening
Highly current limiting for low peak let through current
Improved cycling ability for frequent motor starts/stops without nuisance fuse opening
Rejection style design prevents replacement errors (when used with recommended fuse blocks)
High visibility orange label ensures instant brand recognition, simplifies replacement
Metal embossed date and catalog number for traceability and lasting identification
Fiberglass body provides dimensional stability in harsh industrial settings
High grade silica filler ensures fast arc quenching and optimum current limitation